DSCA49, Analog Input Signal Conditioner DIN Rail Output Modules
- Accepts High-Level Voltage Input
- Provides High-Level Voltage Outputs to ±10V at 50mA
- Analog Output Module
- 1500 Vrms Transformer Isolation
- True 3-Way Isolation
- Accuracy: ± 0.05%
- DIN Rail Mounted Module
- ANSI/IEEE C37.90.1 Transient Protection
- Output Protected to 240 V AC Continuous
- C-UL-US Listed
- CE and ATEX Compliant
Each DSCA49 voltage output module provides a single channel of analog output. The input signal is buffered, isolated, filtered and converted to a voltage output (Figure 1). Signal filtering is accomplished with a five-pole filter which provides 100dB per decade of attenuation above 1kHz. An anti-aliasing pole is located on the system side of the isolation barrier, and the other four poles are on the field side. After the initial system-side filtering, the input signal is chopped by a proprietary chopper circuit. Isolation is provided by transformer coupling, again using a proprietary technique to suppress transmission of common mode spikes or surges.
Special output circuits provide protection against accidental connection of power-line voltages up to 240VAC and against transient events as defined by ANSI/IEEE C37.90.1. Protection circuits are also present on the signal input and
power input terminals to guard against transient events and power reversal. Signal and power lines are secured to the module using screw terminals which are in pluggable terminal blocks for ease of system assembly and reconfiguration.
The modules have excellent stability over time and do not require recalibration, however, zero and span settings are adjustable up to ±5% to accommodate situations where fine-tuning is desired. The adjustments are made using potentiometers located under the front panel label and are non-interactive for ease of use.
Input Type | 0 - 10 V DC |
±10 V DC | |
# of Inputs | 1 |
Output Type | 0 - 10 V DC |
±10 V DC | |
Max Bandwidth | 1 kHz |
Isolation | Yes |
Supply Power | 19 - 29 V DC |
DSCA49-04 | 0-10 V Input, ± 10 V Output |
DSCA49-05 | ± 10 V Input, ± 10 V Output |
DSCA49-06 | ± 10 V Input, 0-10 V Output |
DSCA49 V2 Datasheet |
DSCA49 Datasheet |
DSCA Series Datasheet |
DSCA Dimensions Drawings |
DSCA Calibration Procedure App Note |
AN101 RMS_Voltage_Current App Note |
AN105 Resistance Temperature Detector V2 App Note |
AN121 RiseTime vs BW App Note |
AN126 Tuning_Surge_Tank_Level_Control_Loops App Note |
AN127 OP-Amp Errors, another View App Note |
AN128 RMS Revisited App Note |
AN129 Harmonics and utility costs App Note |
AN801 DSCA Calibration Procedure App Note |
Hysteresis Specifications Tech Note |
Faraday's Law of Induction Tech Note |
Data Acquisition Systems Accessories Tech Note |
Signal Conditioner Surge Withstand Capability Tech Note |
Signal-to-Noise Ratio, SNR Tech Note |
Signal Conditioning Measured vs Combinational Error Tech Note |
When Good Grounds Go Bad Tech Note |
Sample Test Report Tech Note |
Why Isolation (White Paper) Tech Note |
Why Should Sensors Be Isolated Tech Note |
- Strain Gauge & Potentiometer Input Amplifier
- 50 V Continuous Isolation
- Accuracy: ± 0.05%
- DIN Rail Mounted
- In-Line Amplifier (Option)
- Aluminum Housing
- Protection Class: IP40
Input Type | 0 - 10 mV DC, 0 - 100 mV DC, 0 - 1 V DC, 0 - 10 V DC, ±10 V DC, Potentiometer, Strain Gauge |
# of Inputs | 1 |
Output Type | ±5 V DC, ±10 V DC, 0 - 20 mA, 4 - 20 mA |
Max Bandwidth | 1 kHz, 4 kHz |
Excitation | 2.5 V DC, 5 V DC, 10 V DC |
Isolation | Yes |
- Precisely regulated excitation
- Chopper-stabilized low-drift amplification
- Selectable low-pass active filtering
- Front panel setup configuration & calibration
- Wide input range from 50 mv to 50 Vdc FS & 4-20mA
Input Type | ±50 mV to ±50 V DC, 4 - 20 mA |
# of Inputs | 1 |
Output Type | ±5 V DC, ±10 V DC, 4 - 20 mA |
Max Bandwidth | 1 kHz |
Excitation | 10 V DC |
Isolation | Yes |
- Accuracy: ± 0.01%
- DIN Rail Mounted
- Protection Class: IP31
- Thermal Shift : 25 ppm of F.S.
Input Type | ±10 mV DC, ±30 mV DC, ±50 mV DC, ±100 mV DC |
# of Inputs | 1 |
Output Type | ±10 V DC, 4 - 20 mA |
Max Bandwidth | 1 kHz, 10 kHz |
Excitation | 5 V DC, 10 V DC |
Supply Power | 14 - 26 V DC |
- Voltage Input Module
- 1500 V Transformer Isolation
- True 3-Way Isolation
- Accuracy: ± 0.03%
- DIN Rail Mounted Module
- ANSI/IEEE C37.90.1 Transient Protection
- Input Protected to 240 V AC Continuous
Input Type | 0 - 10 mV DC, 0 - 50 mV DC, 0 - 100 mV DC, ±10 mV DC, ±50 mV DC, ±100 mV DC |
# of Inputs | 1 |
Output Type | 0 - 10 V DC, ±10 V DC, 0 - 20 mA, 4 - 20 mA |
Max Bandwidth | 3 Hz |
Isolation | Yes |
Supply Power | 15 - 30 V DC |
- Accepts High-Level Voltage Input
- 1500 Vrms Transformer Isolation
- True 3-Way Isolation
- Accuracy: ± 0.03% or ± 0.05%
- ANSI/IEEE C37.90.1 Transient Protection
- Output Protected to 240VAC Continuous
- Easily Mounts on Standard DIN Rail
- C-UL-US Listed
Input Type | 0 - 10 V DC, ±10 V DC, 0 - 20 mA |
# of Inputs | 1 |
Output Type | 0 - 20 mA, 4 - 20 mA, ±20 mA |
Max Bandwidth | 1 kHz |
Isolation | Yes |
Supply Power | 15 - 30 V DC, 19 - 29 V DC |