DSCT32, Analog Current Input Transmitters


- Accepts Milliamp Level Signals
- Process Current Output
- 1500Vrms Transformer Isolation
- ANSI/IEEE C37.90.1 Transient Protection
- Input and Output Protected to 240VAC Continuous
- Up to 60V Loop Voltage
- 160dB CMR
- NMR, 80dB Per Decade Above 100Hz
- ±0.03% Accuracy
- ±0.01% Linearity
- Easily Mounts on Standard DIN Rail
- CSA and FM Approvals Pending
- CE Compliant
Each DSCT32 current input transmitter provides a single channel of analog input which is filtered, isolated, amplified, and converted to a process current output. Signal filtering is accomplished with a five-pole filter, which provides 80dB per decade of normal-mode rejection above 100Hz. An anti-aliasing pole is located on the field side of the isolation barrier, and the other four are on the process loop side. After the initial field-side filtering, the input signal is chopped by a proprietary chopper circuit. Isolation is provided by transformer coupling, again using a proprietary technique to suppress transmission of common mode spikes or surges.
Special input and output circuits on the DSCT32 transmitters provide protection against accidental connection of power-line voltages up to 240VAC and against transient events as defined by ANSI/IEEE C37.90.1. Signal and loop power lines are secured to the module using screw terminals, which are in pluggable terminal blocks for ease of system assembly and reconfiguration.
The modules have excellent stability over time and do not require recalibration, however, zero and span settings are adjustable up to ±10% to accommodate situations where fine-tuning is desired. The adjustments are made using potentiometers located under the front panel label and are non-interactive for ease of use.
Input Type | 0 - 20 mA |
4 - 20 mA | |
# of Inputs | 1 |
Output Type | 4 - 20 mA |
Max Bandwidth | 100 Hz |
Isolation | Yes |
Supply Power | 12 - 60 V DC |
DSCT32-02 | Input Range: 0 to 20 mA |
DSCT32-01 | Input Range: 4 to 20 mA |
DSCT32 Analog Current Transmitter V2 Datasheet |
DSCT32 Datasheet |
DSCT Diagram Drawings |
DSCT Intro Brochure |
AN101 RMS_Voltage_Current App Note |
AN105 Resistance Temperature Detector V2 App Note |
AN121 RiseTime vs BW App Note |
AN126 Tuning_Surge_Tank_Level_Control_Loops App Note |
AN127 OP-Amp Errors, another View App Note |
AN128 RMS Revisited App Note |
AN129 Harmonics and utility costs App Note |
Hysteresis Specifications Tech Note |
Data Acquisition Systems Accessories Tech Note |
Faraday's Law of Induction Tech Note |
Signal Conditioner Surge Withstand Capability Tech Note |
Sample Test Report Tech Note |
Signal-to-Noise Ratio, SNR Tech Note |
Signal Conditioning Measured vs Combinational Error Tech Note |
When Good Grounds Go Bad Tech Note |
Why Should Sensors Be Isolated Tech Note |
- Current Input Module
- 1500 V Transformer Isolation
- True 3-Way Isolation
- Accuracy: ± 0.03%
- DIN Rail Mounted Module
- ANSI/IEEE C37.90.1 Transient Protection
- Input Protected to 240 V AC Continuous
Input Type | 0 - 20 mA, 4 - 20 mA, ±20 mA |
# of Inputs | 1 |
Output Type | 0 - 10 V DC, ±10 V DC, 0 - 20 mA, 4 - 20 mA |
Max Bandwidth | 100 Hz |
Isolation | Yes |
Supply Power | 15 - 30 V DC |
- Process Monitor, for process signals
- Extremely fast digital transducer
- Isolated Versions Available
- USB Connectivity for easy calibration
- DAQ Mode with a measuring rate - up to 7500 measurements per second
- 2 Button teach-in for Potentiometer
- Teach-in, allows easy setting of both min. and max. of the measuring range
- Output: 4…20 mA/0…10 V
Interface | USB |
Input Type | 0 - 10 V DC, 0 - 20 mA, 4 - 20 mA |
# of Inputs | 1 |
Output Type | 0 - 10 V DC, 4 - 20 mA, RS-485 |
Excitation | 15 V DC, 24 V DC |
Isolation | Yes |
- Precisely regulated excitation
- Chopper-stabilized low-drift amplification
- Selectable low-pass active filtering
- Front panel setup configuration & calibration
- Wide input range from 50 mv to 50 Vdc FS & 4-20mA
Input Type | ±50 mV to ±50 V DC, 4 - 20 mA |
# of Inputs | 1 |
Output Type | ±5 V DC, ±10 V DC, 4 - 20 mA |
Max Bandwidth | 1 kHz |
Excitation | 10 V DC |
Isolation | Yes |
- Programmable Isolated Transmitters
- DC Voltmeter and ammeter
- Teach- In, Digital Filter, Tare
- Output: 0/4...20 mA/0...5 mA/0...2/5/10 V/10V
- Power Supply 10...30 V AC/DC
- Option: Comparators, Data Output, USB Interface
- Isolated
- Accuracy: ±0,15 % of range (for 20 meas./s)
Interface | USB |
Input Type | ±25 V DC, ±50 V DC, ±100 V DC, ±200 V DC, ±400 V DC, ±1 A, ±5 A |
# of Inputs | 1 |
Output Type | 0 - 2 V DC, 0 - 5 V DC, 0 - 10 V DC, ±10 V DC, 0 - 5 mA, 0 - 20 mA, 4 - 20 mA, RS-485 |
Isolation | Yes |
Supply Power | 10 - 30 V DC, 10 - 30 V AC |
- DC Voltmeter and Ammeter
- Transmitters have galvanic separation with isolation voltage of 600 V
- By trimmers accessible from the face of the transmitter we may adjust the range of output signal within the range of ±10%
- Accuracy: ±0,1 % of range
- 35 mm wide DIN Rail Mount
- Rating: IP 20
Input Type | 0 - 450 V DC, 0 - 5 A |
# of Inputs | 1 |
Output Type | 0 - 2 V DC, 0 - 5 V DC, 0 - 10 V DC, ±10 V DC, 0 - 20 mA, 4 - 20 mA, ±20 mA |
Excitation | 5 - 24 V DC |
Isolation | Yes |
Supply Power | 10 - 30 V DC, 10 - 30 V AC, 80 - 250 V AC |