Loading...
A-Tech Instruments Ltd.
Français   |   Welcome. Please Register an Account or Login

BasicLine BL 513, DIN Rail Signal Isolator

DIN-rail isolator for standard analog signals with selectable input/output ranges, galvanic 3-port isolation, and universal supply (24 V DC or 100–230 V AC).
BasicLine BL 513, DIN Rail Signal Isolator
BasicLine BL 513, DIN Rail Signal Isolator
Features:
  • Universal input ranges: 0–20 mA, 4–20 mA, 0–10 V (calibrated switching)
  • Matching output ranges: 0–20 mA, 4–20 mA, 0–10 V
  • Galvanic 3-port isolation (input/output/power supply), 1.5 kV test voltage
  • Cutoff frequency > 100 Hz
  • Gain error < 0.3 % full scale
  • Power supply: 24 V DC or 100–230 V AC (48–62 Hz)
  • Slim DIN-rail housing, 12.5 mm width
Manufacturer:  Knick Interface
Quote
Datasheet
Description
Specifications
Applications
Downloads
Similar Products
BasicLine BL 513 - Description

The BasicLine BL 513 is a compact DIN-rail signal isolator designed for reliable transmission of standard analog signals in industrial applications. It accepts current (0–20 mA, 4–20 mA) or voltage (0–10 V) inputs and provides the same signal types at the output, enabling easy conversion and isolation between field and control levels.

The BL 513 provides galvanic 3-port isolation between input, output, and power supply, eliminating ground loops and ensuring accurate measurements even in noisy environments. With a cutoff frequency greater than 100 Hz and a low gain error of less than 0.3 % full scale, the BL 513 guarantees stable, interference-free signal processing.

It features a universal power supply, operating either from 24 V DC or directly from 100–230 V AC mains, simplifying integration in diverse systems. Its modular 12.5 mm housing with DIN-rail mounting ensures quick installation while saving panel space.

BasicLine BL 513 - Specifications
Input Type0 - 10 V DC
0 - 20 mA
4 - 20 mA
# of Inputs1
Output Type0 - 10 V DC
0 - 20 mA
4 - 20 mA
Max Bandwidth100 Hz
IsolationYes
Supply Power24 V DC
IP RatingIP 20
Min Temperature0°C
Max Temperature55°C
BasicLine BL 513 - Applications

Applications:

  • Industrial signal isolation and conversion

  • Protection of PLC and PCS inputs

  • Noise reduction in control systems

  • Long-distance analog signal transmission

  • Laboratory and process monitoring systems

BasicLine BL 513 - Downloads
BasicLine BL 513 - Similar Products
  • Input: 0–20 mA or 4–20 mA
  • Two galvanically isolated outputs (0–20 mA or 4–20 mA)
  • Both outputs support up to 400 ohms load each, or 800 ohms combined in series
  • Galvanic 4-port isolation (input, outputs, power supply), 1.5 kV test voltage
  • Gain error < 0.3 % full scale
  • Cutoff frequency > 100 Hz
  • Operating temperature: 0 … +55 °C
  • Slim 6.1 mm DIN-rail housing
Input Type
0 - 10 V AC,
0 - 20 mA
# of Inputs
1
Output Type
0 - 20 mA,
4 - 20 mA
Max Bandwidth
100 Hz
Isolation
Yes
Supply Power
24 V DC
  • Compatible with Pt100, Pt1000, and thermocouples (J, K)
  • Automatic recognition of 2-, 3-, or 4-wire RTD connections
  • Output options: 0(4)–20 mA, 0–10 V, 0–5 V
  • 6 mm slim modular housing, DIN-rail mounting
  • Galvanic 3-port isolation between input, output, and power supply
  • High measurement accuracy with innovative circuit design
  • CE compliant and UL approved
Input Type
Thermocouple
# of Inputs
1
Output Type
0 - 5 V DC,
0 - 10 V DC,
0 - 20 mA,
4 - 20 mA
Max Bandwidth
3 Hz
Isolation
Yes
Supply Power
24 V DC
  • Loop-powered design (no separate power supply required)
  • Input/Output: 0–20 mA or 4–20 mA
  • Galvanic isolation between input and output, 1.5 kV test voltage
  • Accuracy: < 0.2 % full scale
  • Low voltage drop: approx. 1.7 V at 20 mA
  • Cutoff frequency > 100 Hz
  • Operating temperature: 0 … +55 °C
  • Available in 1-channel (BL 541) or 2-channel (BL 542) versions
Input Type
0 - 20 mA,
4 - 20 mA
# of Inputs
1,
2
Output Type
0 - 20 mA,
4 - 20 mA
Max Bandwidth
100 Hz
Isolation
Yes
IP Rating
IP 20
  • Process Monitor, for process signals
  • Extremely fast digital transducer
  • Isolated Versions Available
  • USB Connectivity for easy calibration
  • DAQ Mode with a measuring rate - up to 7500 measurements per second
  • 2 Button teach-in for Potentiometer
  • Teach-in, allows easy setting of both min. and max. of the measuring range
  • Output: 4…20 mA/0…10 V
Interface
USB
Input Type
0 - 10 V DC,
0 - 20 mA,
4 - 20 mA
# of Inputs
1
Output Type
0 - 10 V DC,
4 - 20 mA,
RS-485
Excitation
15 V DC,
24 V DC
Isolation
Yes
  • Programmable Isolated Transmitters
  • DC Voltmeter and ammeter
  • Teach- In, Digital Filter, Tare
  • Output: 0/4...20 mA/0...5 mA/0...2/5/10 V/10V
  • Power Supply 10...30 V AC/DC
  • Option: Comparators, Data Output, USB Interface
  • Isolated
  • Accuracy: ±0,15 % of range (for 20 meas./s)
Interface
USB
Input Type
±25 V DC,
±50 V DC,
±100 V DC,
±200 V DC,
±400 V DC,
±1 A,
±5 A
# of Inputs
1
Output Type
0 - 2 V DC,
0 - 5 V DC,
0 - 10 V DC,
±10 V DC,
0 - 5 mA,
0 - 20 mA,
4 - 20 mA,
RS-485
Isolation
Yes
Supply Power
10 - 30 V DC,
10 - 30 V AC
Products    |    Applications    |    Services    |    Partners    |    About Us    |    Contact Us